FIRERAY 2000 EExd Hazardous Area Smoke Detector Installation Guide Page 1 of 12 KEY FEATURES Flameproof Receiver and Transmitter
Page 10 of 12 -VE +VE Do not route wiring within the 50mm circular central area, to avoid obscuring optical components Internal Earth stud will
Page 11 of 12 This page left intentionally blank
Page 12 of 12 FIRERAY 2000 EExd - SYSTEM SPECIFICATION SYSTEM TYPE Transmitter (TX) Rugged for EExd IIB areas - IP67 Receiver (RX) Rugged fo
Page 2 of 12 STATEMENT OF INTENDED USE This system is intended for use as a Smoke Detector only, in EExd IIB, or lower grade areas. It must not
Page 3 of 12 WARNING The area into which the Fireray parts are to be fitted must be made safe before attempting any work on the system. It must
Page 4 of 12 Two possible actions are selectable, once the system has exhausted all compensation steps, as follows:- Leave the COMP switch in
Page 5 of 12 During installation, no threshold switch set at the Controller Unit (One switch only must be set). Possible Causes Of FIRE And
Page 6 of 12 screws, between the Receiver Case and the mounting surface. (Some applications may require fabrication of angled mounting brackets e
Page 7 of 12 TESTING THE SYSTEM Following installation, test the system as follows :- First ensure that the system is running and has been al
Page 8 of 12 RxHIGHLAMPLOWLAMPRELAY WIRING,CONNECT AS REQUIREDTO INDICATINGEQUIPMENTTEST/RESETON OFFSW5+V RxSIGNAL Rx0V RxTESTMETEREXTERNALRESE
Page 9 of 12 1020406080100 TRANSMITTER REQUIRES 2 CORE SCREENED WIRING TO SUITABLE POWER SUPPLY, PLUS ENCLOSURE EARTH BONDING. THE ENCLOSURE